Last Modified: Aug 01, 2024
Affected Product(s):
F5OS F5OS, F5OS-A
Known Affected Versions:
F5OS-A 1.0.0, F5OS-A 1.0.1, F5OS-A 1.1.0, F5OS-A 1.1.1, F5OS-A 1.2.0, F5OS-A 1.3.0, F5OS-A 1.3.1, F5OS-A 1.3.2, F5OS-A 1.4.0, F5OS-A 1.5.0, F5OS-A 1.5.1, F5OS-A 1.5.2
Fixed In:
F5OS-A 1.7.0
Opened: Apr 12, 2023 Severity: 3-Major
If two Murata M1845 AC PSUs are installed in the system and one is operating with an AC input at or above 100V and the second is operating with an AC input below 100V, then an incorrect PSU mismatch condition may occur. Use the F5OS command "show components" to view voltage details for the PSUs.
An incorrect "PSU mismatch" condition may occur.
Two Murata M1845 AC PSUs, one with an AC input at or above 100V and the other with an AC input below 100V.
Ensure both Murata M1845 AC PSUs have input voltage at or above 100V or below 100V.
There is no PSU mismatch for two M1845 PSUs that are operating at different AC input voltages.